• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
DETERMINATION OF REPAIRABILITY
HYDROSTATIC TEST OF CO2 CYLINDERS

Aircrew Survival Equipmentman 2 - Aviation theories and other practices
Page Navigation
  114    115    116    117    118  119  120    121    122    123    124  
the life raft. Remember to take into consideration the inflated size of the raft; an LRU-15/A will take 20 times the area that an LR-1 requires. To begin the test, you first open the carrying case and unfold the life raft. All life rafts have an inflation assembly, and by pulling an actuating cable, you automatically inflate the raft with CO2. When you do this, the raft should inflate to design shape, without evidence of restriction, in less than 1 minute. This is a CDI inspection point, so have a CDI inspector watching before you pull the cable. Once the raft is inflated, examine it for obvious defects such as cuts, tears, ruptured seams, and damaged manifold. PULL CABLE PROOF LOAD TEST FOR MULTIPLACE RAFTS The pull cable proof load test for multiplace rafts is done in conjunction with the functional test. Also, the test must be performed prior to placing an inflation assembly into service. First remove the inflation valve cover plate and remove the pull cable from the valve. Then apply a 50-pound pull force between the cable ball and the snap hook to determine if the cable is strong enough for the system. Examine the pull cable for broken strands of wire, deformed snap hook, security of snap hook spring latch attachment, and loose or cracked swage fittings. If any damage is found, the pull cable is discarded and replaced with a new cable. The new cable is also tested. If the snap hook spring latch is loose, it may be repaired in accordance with instructions contained in NAVAIR 13-1-6.1. If the pull cable passes this test, reinstall the cable. Refer to NAVAIR 13-1-6.1 for details of installation. LEAKAGE TESTING The only way that you can be sure that a life raft does not have a leak is to perform a leakage test. To test the LRU-15/A with a vented Y- manifold for leakage, you must ensure that either the manifold inlet is capped or an empty cylinder is installed and the manifold inlet is in the CLOSED position. Install an equalizer tube clamp. These procedures are necessary for this raft due to its design. The LRU-15/A has two flotation tubes; one is on top of the other. The equalizer tube allows C02 or air pressure to enter both tubes at the same time. If you fail to cap the inlet, you will not be able to hold the pressure within the flotation tube. If you don’t use an equalizer clamp, you will blow up both flotation tubes. NOTE: Flotation tubes must be tested separately to determine internal vertical bulkhead leakage. All multiplace life rafts are filled with air pressure through the topping-off valves. The LR-1 is inflated through an oral inflation tube. After you have reached the test pressure (table 6-1), shut off the air supply and wait 15 minutes. Table 6-1.-Life Raft Test Pressures 6-3







Western Governors University

Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved. Design by Strategico.