Figure 8-20.--SSDG OUTPUT AND DISTRIBUTION panel (A-8).
It displays a mimic bus depicting the physical
describe the switch/indicators from the left to
arrangement of the electric plant and BTs. The
right, and then down.
panel is divided into four sections, one for each
SSDG (4, 2, 3, and 1). Each section is the same.
MANUAL START/AUTO START is a
The panel contains the controls and indicators
split-legend, alternate-action push-button
used to start and stop the SSDG and to control
switch. When the MANUAL START posi-
the opening and closing of the generator, BTs,
tion of the indicator is illuminated, the
and load shedding CB; it also has an indicator
operator must start the SSDG. If the
indicating the SWBD control location.
AUTO START position of the indicator
is illuminated, the control of starting the
SSDG is given to the SCS.
Engine Starting and Stopping Section
PRIME MOVER 1 START is a push
The engine starting and stopping section is
button used to start the SSDG. It is
located across the top of each section. We will
8-41