pneumatic pressure and is opened by pneumatic
signals from a remotely located avionics ram air
servo. Pressure is supplied from the servo to hold
the valve closed. When externally supplied
pressure from the servo drops below a specified
value, the valve opens and supplies ram air.
ECM Cooling Air Control Valve
The ECM cooling air control valve is a two-
position solenoid controlled valve. The valve
provides a high flow of cooling air to the
electronic countermeasure (ECM) package when
de-energized and a low flow when energized. The
valve is energized when the ECM mode switch on
the ECM control panel assembly is selected to
OFF or STBY.
Avionics Ground Cooling Fan
The avionics ground cooling fan is an
electrically driven axial flow fan that provides a
flow of ambient air for direct avionics cooling
during aircraft ground operation, taxi, takeoff,
and landing. The fan is in the nose wheelwell and
is powered by an induction motor.
Avionics Ground Cooling Fan Check Valve
The avionics ground cooling fan check valve
is made up of two spring-loaded flappers hinged
around a central shaft. The check valve is located
between the upper and lower plenums, and it
functions to prevent cooling air from escaping
through the avionics ground cooling fan during
flight.
Avionics Fan Control Pressure Switch
The avionics fan control pressure switch is a
pneumatically operated switch in the ducting
downstream of the primary heat exchanger. This
switch controls the avionics ground cooling fan
operation to provide supplemental air for avionics
equipment cooling.
Emergency Ram Air Scoop
The emergency ram air scoop is a spring-
loaded scoop on the forward fuselage. The scoop
is held closed by a solenoid, which releases the
scoop when energized. A linkage arrangement,
connected to the scoop, closes a flapper on the
avionics cooling plenum and directs ram air to the
essential avionics when the scoop is opened. The
3-16
FCS cool switch, on the right vertical console,
activates the scoop release solenoid when set to
EMERG.
Avionics Undercool Warning
Temperature Sensor
The avionics undercool/warning temperature
sensor is made up of two temperature sensing
elements, one is self-heated. On detecting an
undercool condition of avionics cooling air, the
sensor sends a signal to the signal data converter,
which displays the AV AIR HOT caution message
on the left digital display indicator.
Avionics Cooling Fans
The two avionics cooling fans in the cockpit
are axial flow fans driven by electric motors. Both
fans operate continuously with any ground power
switch to A ON or B ON or flt cent switch to ON.
Individual cockpit fan operation can be verified
by setting the fan test switch on the fan test
control panel assembly to A LEFT or B RIGHT.
Rear Cockpit Avionics Cooling Fans
The rear cockpit avionics cooling fans are
identical in design and function to the cockpit
avionics cooling fans. Individual rear cockpit fan
operation can be verified by setting the fan test
switch on the fan test control and utility light
panel assembly to A LEFT or B RIGHT.
VAPOR CYCLE AIR-CONDITIONING
SYSTEM
Vapor cycle systems make use of the scientific
fact that a liquid can be vaporized at any
temperature by changing the pressure above it.
Water at sea level barometric pressure of 14.7 psi
will boil at 212°F. The same water in a closed tank
under a pressure of 90 psi will not boil at less than
320°F. If the pressure is reduced to 0.95 psi by
a vacuum pump, the water would boil at 100°F.
If the pressure is reduced further, the water would
boil at a still lower temperature; for instance, at
0.12 psi, water will boil at 40°F. Water can be
made to boil at any temperature if the pressure
corresponding to the desired boiling temperature
can be maintained.
Liquids that boil at low temperatures are the
most desirable for use as refrigerants. Com-
paratively large quantities of heat are absorbed
when liquids are evaporated; that is, changed to